changed task 1 to generic ip address configuration
This commit is contained in:
@@ -23,18 +23,16 @@
|
||||
|
||||
## Tasks to Complete
|
||||
|
||||
1. [Set PLC IP Address on a CompactLogix PLC](tasks/new-hire-task1.html)
|
||||
2. Set PLC IP Address on a Micro800 CompactLogic
|
||||
3. Set HMI IP Address on a Panelview 800 HMI
|
||||
4. Enable VNC Server on Panelview 800 HMI
|
||||
5. Set HMI IP Address on a Panelview Plus 6/7 HMI
|
||||
6. Enable VNC Server on Panelview Plus 6/7 HMI
|
||||
7. Flash the firmware for a device via CompactFlash and RSLinx
|
||||
8. Download a Connected Components Workbench drive file to a VFD
|
||||
9. Download a PLC program to a CompactLogix PLC
|
||||
10. Download a PLC program to a Micro800 PLC
|
||||
11. Upload a PLC Program from a CompactLogic PLC for troubleshooting
|
||||
12. Upload a PLC Program from a Micro800 PLC for troubleshooting
|
||||
13. Add a device to POCloud
|
||||
14. Read Modbus Registers with Micro800 PLC
|
||||
15. Read Modbus Registers wtih CompactLogix PLC + Prosoft Card
|
||||
1. [Set IP Address via RSLinx](tasks/new-hire-task1.html)
|
||||
2. Enable VNC Server on Panelview 800 HMI
|
||||
3. Set HMI IP Address on a Panelview Plus 6/7 HMI
|
||||
4. Enable VNC Server on Panelview Plus 6/7 HMI
|
||||
5. Flash the firmware for a device via CompactFlash and RSLinx
|
||||
6. Download a Connected Components Workbench drive file to a VFD
|
||||
7. Download a PLC program to a CompactLogix PLC
|
||||
8. Download a PLC program to a Micro800 PLC
|
||||
9. Upload a PLC Program from a CompactLogic PLC for troubleshooting
|
||||
10. Upload a PLC Program from a Micro800 PLC for troubleshooting
|
||||
11. Add a device to POCloud
|
||||
12. Read Modbus Registers with Micro800 PLC
|
||||
13. Read Modbus Registers wtih CompactLogix PLC + Prosoft Card
|
||||
|
||||
@@ -1,4 +1,4 @@
|
||||
# Task 1 - CompactLogic PLC IP Address
|
||||
# Task 1 - IP Address via RSLinx
|
||||
|
||||
## Equipment Needed
|
||||
|
||||
@@ -8,11 +8,11 @@
|
||||
|
||||
## Assumptions
|
||||
|
||||
This tutorial assumes that the PLC is being assigned an IP address by a DHCP server. Henry Pump shop computers are configured with a DHCP server to assign IP addresses on the 192.168.1.0 network.
|
||||
The Ethernet procedure assumes that the device is being assigned an IP address by a DHCP server. Henry Pump shop computers are configured with a DHCP server to assign IP addresses on the 192.168.1.0 network.
|
||||
|
||||
## Procedure (Ethernet)
|
||||
|
||||
1. Ensure your PC IP Address is a member of the same subnet as the PLC.
|
||||
1. Ensure your PC IP Address is a member of the same subnet as the device.
|
||||
2. Open RSLinx Classic
|
||||
3. If there is already an EtherNet\IP Devices driver setup, skip to step 9.
|
||||
4. Click the "Configure Drivers" button or navigate to "Communications > Configure Drivers".
|
||||
@@ -22,7 +22,26 @@ This tutorial assumes that the PLC is being assigned an IP address by a DHCP ser
|
||||
8. Close the "Configure Drivers" window.
|
||||
9. Click the RSWho button or navigate to "Communications > RSWho".
|
||||
10. Expand the EtherNet\IP Devices driver to begin browsing the network.
|
||||
11. Locate the CompactLogix PLC in the browse list.
|
||||
12. Right-click on the PLC and select "Module Configuration".
|
||||
11. Locate the device in the browse list.
|
||||
12. Right-click on the device and select "Module Configuration".
|
||||
13. In the "Port Configuration" Tab, select to "Manually configure IP settings" and input the desired IP settings. Click OK.
|
||||
14. Verify in the browse list that the PLC is now using the correct IP Address.
|
||||
14. Verify in the browse list that the device is now using the correct IP Address.
|
||||
|
||||
|
||||
## Procedure (USB)
|
||||
|
||||
1. Open RSLinx Classic
|
||||
2. Expand the USB driver to begin browsing the network.
|
||||
3. Locate the device in the browse list.
|
||||
4. Right-click on the device and select "Module Configuration".
|
||||
5. In the "Port Configuration" Tab, select to "Manually configure IP settings" and input the desired IP settings. Click OK.
|
||||
6. Connect an ethernet cable from the PC to the device and ensure that the PC has an IP Address on the same subnet as the device.
|
||||
7. If there is already an EtherNet\IP Devices driver setup, skip to step 9.
|
||||
8. Click the "Configure Drivers" button or navigate to "Communications > Configure Drivers".
|
||||
9. Under "Available Driver Types" select "EtherNet\IP Devices" and click "Add New..."
|
||||
10. Choose a name for the driver or leave it as the default.
|
||||
11. Select which network port to use for the driver. This is typically "Windows Default" or the Ethernet Port.
|
||||
12. Close the "Configure Drivers" window.
|
||||
13. Click the RSWho button or navigate to "Communications > RSWho".
|
||||
14. Expand the EtherNet\IP Devices driver to begin browsing the network.
|
||||
15. Verify in the browse list that the device is now using the correct IP Address.
|
||||
|
||||