## Equipment Needed
|
||||
|
||||
- RSLinx Classic
|
||||
- Ethernet Cable
|
||||
- (Optional) USB Cable
|
||||
- RSLinx Classic
|
||||
- Ethernet Cable
|
||||
- (Optional) USB Cable
|
||||
|
||||
## Procedure
|
||||
## Assumptions
|
||||
|
||||
(TO BE ADDED SOON)
|
||||
This tutorial assumes that the PLC is being assigned an IP address by a DHCP server. Henry Pump shop computers are configured with a DHCP server to assign IP addresses on the 192.168.1.0 network.
|
||||
|
||||
## Procedure (Ethernet)
|
||||
|
||||
1. Ensure your PC IP Address is a member of the same subnet as the PLC.
|
||||
2. Open RSLinx Classic
|
||||
3. If there is already an EtherNet\IP Devices driver setup, skip to step 9.
|
||||
4. Click the "Configure Drivers" button or navigate to "Communications > Configure Drivers".
|
||||
5. Under "Available Driver Types" select "EtherNet\IP Devices" and click "Add New..."
|
||||
6. Choose a name for the driver or leave it as the default.
|
||||
7. Select which network port to use for the driver. This is typically "Windows Default" or the Ethernet Port.
|
||||
8. Close the "Configure Drivers" window.
|
||||
9. Click the RSWho button or navigate to "Communications > RSWho".
|
||||
10. Expand the EtherNet\IP Devices driver to begin browsing the network.
|
||||
11. Locate the CompactLogix PLC in the browse list.
|
||||
12. Right-click on the PLC and select "Module Configuration".
|
||||
13. In the "Port Configuration" Tab, select to "Manually configure IP settings" and input the desired IP settings. Click OK.
|
||||
14. Verify in the browse list that the PLC is now using the correct IP Address.
|
||||
|
||||