121 Commits

Author SHA1 Message Date
Patrick McDonagh
5573de4a88 Adds default configuration file for NAT 2016-08-11 14:51:49 -05:00
Patrick McDonagh
6e03647d38 Completes IPP-110, IPP-111, IPP-112. Display for %FLA, Fix for not reading Frequency or Phase Rotation 2016-08-10 19:22:30 -05:00
Patrick McDonagh
ed19a7d91e Tag Cleanup 2016-08-10 15:13:31 -05:00
Patrick McDonagh
40d02118a5 Updates IP Address in PLC program for behind NAT 2016-08-10 14:14:38 -05:00
Patrick McDonagh
ae150eb329 Updates IP Address in HMI program for behind NAT 2016-08-10 14:03:19 -05:00
Patrick McDonagh
df6a720806 Merge branch 'master' of http://bitbucket.poconsole.net/scm/ipp/pioneer-ipp
# Conflicts:
#	PWM_Water_Meter_Skid_Rev_HP.ACD
2016-08-10 12:00:22 -05:00
Patrick McDonagh
6eb942c83c Completes IPP-108, adding 30 second delay timer for High Pressure Switch 2016-08-10 11:59:08 -05:00
Patrick McDonagh
fea4d0ae27 Updates Ignore File 1.1 2016-08-09 18:27:41 -05:00
Patrick McDonagh
994105555a Don't allow a restart if there is an Overload Trip 2016-08-09 18:17:53 -05:00
Patrick McDonagh
8a8d5b2263 Merge branch 'master' of http://bitbucket.poconsole.net/scm/ipp/pioneer-ipp 2016-08-09 15:05:12 -05:00
Patrick McDonagh
f340a0d4db Adds HMI Alarms for Surface Pressure and Flow, Adds Overall Trip Status to main screen 2016-08-09 08:24:15 -05:00
Patrick McDonagh
fef4d613d0 A few logic changes after IPP-105 2016-08-08 22:30:23 -05:00
Patrick McDonagh
58f38aae0f Configured Alarm Setpoints before installing first panel 2016-08-08 09:57:36 -05:00
Patrick McDonagh
a4acae3b80 Completes IPP-103. Adds Flowmeter_HART_Failure. also adds default E300 config spreadsheet 2016-08-03 17:38:13 -05:00
Patrick McDonagh
e0f65927db Adds UPS and HOA Status to README.md 2016-08-03 14:40:14 -05:00
Patrick McDonagh
eea0b46c4e Completes IPP-101 2016-08-02 14:04:59 -05:00
Patrick McDonagh
b4b4c3ca9c A few changes during meeting with Pioneer 2016-08-02 10:23:06 -05:00
Patrick McDonagh
65899e97ef Adds Data Table for Ignition 2016-08-01 15:01:04 -05:00
Patrick McDonagh
b4324d5f8b Completes IPP-98 by adding HOA_Status Integer 2016-08-01 14:36:46 -05:00
Patrick McDonagh
45601dd17c Merged branch master into master 2016-07-29 14:25:26 -05:00
Patrick McDonagh
18487a3eb3 Adds all tags available to SCADA to README.md and excel document 2016-07-29 14:25:17 -05:00
Patrick McDonagh
4b9ccd6b76 Completes IPP-55. Adds ability to reset E300 to defaults 2016-07-26 17:10:06 -05:00
Patrick McDonagh
67af129c36 Completes IPP-96, adds Phase Rotation Trip logic 2016-07-26 15:50:18 -05:00
Patrick McDonagh
78413bb0f3 Completes IPP-82, Adds integer and string tags for Overall Trip and Warning Status. See README.md for mapping. 2016-07-26 11:52:40 -05:00
Patrick McDonagh
49ae52726c Adds README.md 2016-07-26 10:41:52 -05:00
Patrick McDonagh
edab6e07f9 Completes IPP-76, Lightning arrestor to be wired to digital input 7, assumed to be N.C. 2016-07-25 18:36:16 -05:00
Patrick McDonagh
23de1fac3f Fixes IPP-73 and completes IPP-74.Daily and Monthly Totals with reset on powerup if day, month, or year has changed 2016-07-25 17:46:29 -05:00
Patrick McDonagh
decab95222 Completes IPP-75, sets time from SCADA. Write to Input_DateTime.Year, .Month, etc. write to Set_PLC_Time to apply it. 2016-07-25 17:04:28 -05:00
Patrick McDonagh
f1ccc3fca1 Fixes IPP-72, Adds watchdog timeout for datalogger. uses tag Datalogger_Watchdog_Timeout 2016-07-25 16:36:24 -05:00
Patrick McDonagh
8640c52565 Completes IPP-71, Alarms on UPS errors. UPS Ready = Digital In 4, UPS Buffering = Digital In 5, UPS Replace Battery = Digital In 6 2016-07-25 15:03:28 -05:00
Patrick McDonagh
79fe78e67c Completes IPP-83, configuration and calculation for fluid level 2016-07-25 14:32:58 -05:00
Patrick McDonagh
42f62a334e PLC and HMI Programming for IPP-70, adding Tubing Pressure Switch (and disable button) wired into digital input 3 2016-07-25 14:24:15 -05:00
Patrick McDonagh
c2efa012fa Completes IPP-78, adding Off Status 2016-07-25 13:45:54 -05:00
Patrick McDonagh
8e95544712 Completes IPP-84, Control routine converted to Ladder for easier troubleshooting 2016-07-25 13:41:51 -05:00
Patrick McDonagh
2789416859 Resolve IPP-81, Returns 0.0 for Intake Temp and Pressure if DH Status is bad 2016-07-25 09:35:45 -05:00
Patrick McDonagh
00b65c9c89 Resolves IPP-77. Sets default Tubing Pressure alarms to Hi: 25, Lo: 125 2016-07-25 09:27:05 -05:00
Patrick McDonagh
2aeecd06da removed unnecessary files 2016-07-15 08:47:11 -05:00
Patrick McDonagh
d8e22a283b Added FreshWater panel program (1 IO module instead of 2) 2016-07-15 08:46:19 -05:00
Patrick McDonagh
feac0be9a6 File Cleanup 2016-07-13 08:03:25 -05:00
Patrick McDonagh
eac3378fec Fixes IPP-60. Fixes Low Tubing Pressure SP 2016-07-11 21:20:14 -05:00
Patrick McDonagh
8d55710b7e Unsets Ignition commands once the intended operation has completed 2016-07-11 18:03:40 -05:00
Patrick McDonagh
87eace08dd Adds IPP-58, ability to configure flow and pressure alarms on HMI 2016-07-11 17:49:36 -05:00
Patrick McDonagh
d494ee0ac3 Fixes IPP-57. Since we'll always have tubing pressure, removed the tag completely 2016-07-11 15:52:45 -05:00
Patrick McDonagh
9d4cf67a7f Fixes IPP-56. Removed WarningEnable tag for Phase Loss 2016-07-11 15:33:03 -05:00
Patrick McDonagh
0b1f96e458 Completes IPP-51. Adds Flow to Downhole screen of the HMI 2016-06-17 10:43:52 -05:00
Patrick McDonagh
bd54bce14c Revamped Logic per IPP-48. Combining Pioneer and Henry Pump logic 2016-06-16 18:51:42 -05:00
Patrick McDonagh
d915e96e18 Fixes IPP-30. When parameters are written to the E300, it gets inhibited and then uninhibited 2016-05-12 23:49:31 -05:00
Patrick McDonagh
59dd4960c7 Committing old file since security was corrupted 2016-05-11 18:16:58 -05:00
Patrick McDonagh
3d31144766 removed that pesky .ccwsuo file from tracking 2016-04-15 14:28:47 -05:00
Patrick McDonagh
7ec73fa27e 55d9676 Added missing E300 parameters that aren't included in Add-On Profile 2016-04-15 09:59:45 -05:00