Joshua Fine
1ed4b717d8 Fixed Totalizer
Found Rung 3 had a OTL in the shift totals instead of an OTE.  Changed to OTE.  Totalizer working correctly now.
2018-09-27 11:11:12 -05:00
Patrick McDonagh
18bc87c49b Adds setup file 2018-08-16 15:47:24 -05:00
Patrick McDonagh
722413799e Fix for "Module Not Configured" Error
Rockwell bullshit
2018-08-10 13:19:28 -05:00
Patrick McDonagh
915451d945 Fixes PWM Frequency default value 2018-06-27 11:28:51 -05:00
Patrick McDonagh
35a9dd0648 Adds POCloud support for HART totalizer data 2018-06-22 14:35:10 -05:00
Patrick McDonagh
0ebd786962 Turns off Simulation Mode for default 2018-06-22 13:01:30 -05:00
Patrick McDonagh
41badb4348 Adds HART + failover for pressure transmitter 2018-06-22 12:07:03 -05:00
Patrick McDonagh
1fec3011ab Switches Analog IO to HART-enabled 2018-06-21 13:08:56 -05:00
Patrick McDonagh
6aeb27a4fc Merge branch 'master' of https://github.com/Henry-Pump/Max-Water-System 2018-06-14 11:56:21 -05:00
Patrick McDonagh
b9d581b2a1 Fix for PLC-VFD connection after rockwell fucked it up
- getting "16#0010 Connection Request Error Module Not Configured" error even though module was configured.
- error occurs when Studio5000 upgraded from V30 to V31
2018-06-14 11:53:37 -05:00
Patrick McDonagh
498f87d4ee Move files and folders around for uniform convention 2018-05-22 11:58:57 -05:00
144 changed files with 37810 additions and 21343 deletions

File diff suppressed because one or more lines are too long

17730
MaxWaterSystem_SetUp.ACD Normal file

File diff suppressed because one or more lines are too long

View File

@@ -1,4 +0,0 @@
"""Simulate a water well."""
flowrate_in = 100 # GPM, typically unknown and changing

16520
PLC/MaxWaterSystem.ACD Normal file

File diff suppressed because one or more lines are too long

Some files were not shown because too many files have changed in this diff Show More