Patrick McDonagh
|
edab6e07f9
|
Completes IPP-76, Lightning arrestor to be wired to digital input 7, assumed to be N.C.
|
2016-07-25 18:36:16 -05:00 |
|
Patrick McDonagh
|
23de1fac3f
|
Fixes IPP-73 and completes IPP-74.Daily and Monthly Totals with reset on powerup if day, month, or year has changed
|
2016-07-25 17:46:29 -05:00 |
|
Patrick McDonagh
|
decab95222
|
Completes IPP-75, sets time from SCADA. Write to Input_DateTime.Year, .Month, etc. write to Set_PLC_Time to apply it.
|
2016-07-25 17:04:28 -05:00 |
|
Patrick McDonagh
|
f1ccc3fca1
|
Fixes IPP-72, Adds watchdog timeout for datalogger. uses tag Datalogger_Watchdog_Timeout
|
2016-07-25 16:36:24 -05:00 |
|
Patrick McDonagh
|
8640c52565
|
Completes IPP-71, Alarms on UPS errors. UPS Ready = Digital In 4, UPS Buffering = Digital In 5, UPS Replace Battery = Digital In 6
|
2016-07-25 15:03:28 -05:00 |
|
Patrick McDonagh
|
79fe78e67c
|
Completes IPP-83, configuration and calculation for fluid level
|
2016-07-25 14:32:58 -05:00 |
|
Patrick McDonagh
|
42f62a334e
|
PLC and HMI Programming for IPP-70, adding Tubing Pressure Switch (and disable button) wired into digital input 3
|
2016-07-25 14:24:15 -05:00 |
|
Patrick McDonagh
|
c2efa012fa
|
Completes IPP-78, adding Off Status
|
2016-07-25 13:45:54 -05:00 |
|
Patrick McDonagh
|
8e95544712
|
Completes IPP-84, Control routine converted to Ladder for easier troubleshooting
|
2016-07-25 13:41:51 -05:00 |
|
Patrick McDonagh
|
2789416859
|
Resolve IPP-81, Returns 0.0 for Intake Temp and Pressure if DH Status is bad
|
2016-07-25 09:35:45 -05:00 |
|
Patrick McDonagh
|
00b65c9c89
|
Resolves IPP-77. Sets default Tubing Pressure alarms to Hi: 25, Lo: 125
|
2016-07-25 09:27:05 -05:00 |
|
Patrick McDonagh
|
2aeecd06da
|
removed unnecessary files
|
2016-07-15 08:47:11 -05:00 |
|
Patrick McDonagh
|
d8e22a283b
|
Added FreshWater panel program (1 IO module instead of 2)
|
2016-07-15 08:46:19 -05:00 |
|
Patrick McDonagh
|
feac0be9a6
|
File Cleanup
|
2016-07-13 08:03:25 -05:00 |
|
Patrick McDonagh
|
eac3378fec
|
Fixes IPP-60. Fixes Low Tubing Pressure SP
|
2016-07-11 21:20:14 -05:00 |
|
Patrick McDonagh
|
8d55710b7e
|
Unsets Ignition commands once the intended operation has completed
|
2016-07-11 18:03:40 -05:00 |
|
Patrick McDonagh
|
87eace08dd
|
Adds IPP-58, ability to configure flow and pressure alarms on HMI
|
2016-07-11 17:49:36 -05:00 |
|
Patrick McDonagh
|
d494ee0ac3
|
Fixes IPP-57. Since we'll always have tubing pressure, removed the tag completely
|
2016-07-11 15:52:45 -05:00 |
|
Patrick McDonagh
|
9d4cf67a7f
|
Fixes IPP-56. Removed WarningEnable tag for Phase Loss
|
2016-07-11 15:33:03 -05:00 |
|
Patrick McDonagh
|
0b1f96e458
|
Completes IPP-51. Adds Flow to Downhole screen of the HMI
|
2016-06-17 10:43:52 -05:00 |
|
Patrick McDonagh
|
bd54bce14c
|
Revamped Logic per IPP-48. Combining Pioneer and Henry Pump logic
|
2016-06-16 18:51:42 -05:00 |
|
Patrick McDonagh
|
d915e96e18
|
Fixes IPP-30. When parameters are written to the E300, it gets inhibited and then uninhibited
|
2016-05-12 23:49:31 -05:00 |
|
Patrick McDonagh
|
59dd4960c7
|
Committing old file since security was corrupted
|
2016-05-11 18:16:58 -05:00 |
|
Patrick McDonagh
|
3d31144766
|
removed that pesky .ccwsuo file from tracking
|
2016-04-15 14:28:47 -05:00 |
|
Patrick McDonagh
|
7ec73fa27e
|
55d9676 Added missing E300 parameters that aren't included in Add-On Profile
|
2016-04-15 09:59:45 -05:00 |
|
Patrick McDonagh
|
5c9a47bdce
|
archived HMI files
|
2016-04-15 09:58:41 -05:00 |
|
Patrick McDonagh
|
496c6d80c3
|
Fixed trends not holding enough data for full screen
|
2016-04-11 14:35:17 -05:00 |
|
Patrick McDonagh
|
7a4b8df9da
|
Added Remote Start & Run Status
|
2016-04-06 21:25:02 -05:00 |
|
Patrick McDonagh
|
2cfb0ca640
|
Re-exported program and removed unnecessary files
|
2016-04-06 16:43:54 -05:00 |
|
Patrick McDonagh
|
4453783df6
|
Tested Local IO
|
2016-04-06 16:19:27 -05:00 |
|
Patrick McDonagh
|
b2ab02555f
|
Added ability to disable E300 and use local IO for retrofits
|
2016-04-06 16:15:13 -05:00 |
|
Patrick McDonagh
|
ad68f3b6e5
|
Changed E300 revision to 5.1 (was 3.1)
|
2016-04-06 15:13:04 -05:00 |
|
Patrick McDonagh
|
7e44bc338d
|
Fixed E300 Add-On Profile
|
2016-04-06 13:20:06 -05:00 |
|
Patrick McDonagh
|
8903e019a1
|
E300 config paramters was causing faults
|
2016-04-05 21:43:41 -05:00 |
|
Patrick McDonagh
|
d96f84af0b
|
After Install Attempt 1
|
2016-04-05 17:28:49 -05:00 |
|
Patrick McDonagh
|
866cd1be61
|
Added High Precision Temperature and Pressure
|
2016-04-04 17:47:01 -05:00 |
|
Patrick McDonagh
|
55d96766f5
|
Added missing E300 parameters that aren't included in Add-On Profile
|
2016-02-18 19:24:52 -06:00 |
|
Patrick McDonagh
|
325a485df7
|
Got Modbus Card to work, fixed a few errors, exported routine
|
2016-02-18 17:59:33 -06:00 |
|
Patrick McDonagh
|
6532c6dbbd
|
Fixed current screen navigation and enable tags
|
2016-02-16 16:53:53 -06:00 |
|
Patrick McDonagh
|
380b4936be
|
Made changes to get the panel up and running
|
2016-02-16 16:28:47 -06:00 |
|
Patrick McDonagh
|
60be12acf2
|
Merged branch develop into develop
|
2016-02-16 13:02:20 -06:00 |
|
Patrick McDonagh
|
9b11212ec0
|
Updated PLC address
|
2016-02-16 13:00:44 -06:00 |
|
Patrick McDonagh
|
f126cfd464
|
Removed Leftover files
|
2016-02-16 10:47:48 -06:00 |
|
Patrick McDonagh
|
999f8cdb64
|
Combined TCU and FLA screens
|
2016-02-16 08:41:42 -06:00 |
|
Patrick McDonagh
|
843b7ad18e
|
Deleted screens to make application fit for compactlogix
1. OverFrequency
2. Underfrequency
3. Voltage Imbalance
4. CT
5. PT
6. Voltage Mode
7. Underload
8. Undercurrent
9. Phase Rotation
10. Power
11. IO
12. Current Imbalance
|
2016-02-15 07:43:29 -06:00 |
|
Patrick McDonagh
|
c548223066
|
Initial Commit
|
2016-02-12 17:48:23 -06:00 |
|