@@ -8,7 +8,9 @@ Reads from either a modbus flowmeter or an analog flowmeter.
|
||||
- Slot 1: 2080-IF2
|
||||
|
||||
## Inputs
|
||||
|
||||
### Digital Inputs
|
||||
|
||||
| Input | Usage |
|
||||
| ----- | ---------------------------- |
|
||||
| 0 | Flowmeter Type (On = Modbus) |
|
||||
@@ -16,26 +18,32 @@ Reads from either a modbus flowmeter or an analog flowmeter.
|
||||
|
||||
|
||||
### Analog Inputs
|
||||
|
||||
| Input | Usage |
|
||||
|--------- | ----------------- |
|
||||
| 0 | 4-20mA Flowmeter |
|
||||
| 1 | 4-20mA Pressure |
|
||||
|
||||
## Outputs
|
||||
|
||||
### Digital Outputs
|
||||
|
||||
| Output | Usage |
|
||||
| ------ | ----------------------- |
|
||||
| 0 | Analog Flowmeter in use |
|
||||
| 1 | Modbus Flowmeter in use |
|
||||
|
||||
## Configuration
|
||||
|
||||
The system can be configured to use either an Analog Flowmeter or a Modbus Flowmeter. The system defaults to the Analog Flowmeter.
|
||||
|
||||
### To enable the modbus flowmeter do one of the following:
|
||||
|
||||
- Jumper 24VDC to Digital Input 0
|
||||
- Write 1/True to the tag "sw_UseModbusFlowmeter" from SCADA
|
||||
|
||||
### To enable the analog flowmeter do BOTH of the following:
|
||||
|
||||
- Remove the 24VDC jumper from Digital Input 0
|
||||
- Write 0/False to the tag "sw_UseModbusFlowmeter" from SCADA
|
||||
|
||||
@@ -44,6 +52,7 @@ When the system is configured to use the Analog Flowmeter, Digital Output 0 will
|
||||
When the system is configured to use the Modbus Flowmeter, Digital Output 1 will be ON.
|
||||
|
||||
### Customizing Modbus Parameters
|
||||
|
||||
The system defaults for modbus parameters enable communication with the Promag Modbus meters. The following tags can be modified to enable communication with different device types:
|
||||
|
||||
| Tag | Default | Usage |
|
||||
@@ -62,6 +71,7 @@ The system defaults for modbus parameters enable communication with the Promag M
|
||||
The serial port is configured as a Master for Modbus RTU over RS485 with baud rate of 9600, 8N2.
|
||||
|
||||
## SCADA Tags
|
||||
|
||||
The following tags would be relevant to read over SCADA:
|
||||
|
||||
| Tag | Type | Description | Access |
|
||||
@@ -91,5 +101,6 @@ The following tags would be relevant to read over SCADA:
|
||||
| val\_StatusString | STRING | FlowMeter Status | R |
|
||||
|
||||
## Contributors
|
||||
|
||||
- [Patrick McDonagh](https://github.com/patrickjmcd) - Owner
|
||||